電線サイズ 変換ツール

AWG⇔直径・断面積

Required Parameters

Waiting for input data...

Ad Placement
Sidebar Adaptive Ad Slot

Quick Answer

AWG (American Wire Gauge) is a logarithmic scale where lower numbers = thicker wire. The formula d(mm) = 0.127 × 92^((36-AWG)/39) converts any gauge to diameter. Each 3 AWG steps doubles the cross-sectional area and halves the resistance.

Documentation

銉偆銉ゃ兗銈点偆銈鸿▓绠椼儎銉笺儷

AWG銇ㄣ儭銉堛儶銉冦偗mm2銇枔銇у鎻涖仐闆绘祦瀹归噺銈掔⒑瑾嶃仐銇俱仚銆?"@ W "wire-size-conversion.pt.mdx" @"

Calculadora de Bitola de Fio

Converta entre AWG e mm2 metrico.

Design Notes

AWG is used throughout North America while IEC metric sizes (mm²) are standard in Europe and Asia. There is no exact 1:1 mapping between the systems. For current-carrying capacity, always consult your local electrical code (NEC in the US, IEC 60364 internationally) as ampacity depends on installation conditions.

Common Mistakes

  • 1

    Thinking higher AWG = thicker wire. It is the OPPOSITE: AWG 10 is much thicker than AWG 24.

  • 2

    Using the same ampacity rating for wire in conduit vs free air — bundled wires must be derated significantly.

  • 3

    Ignoring voltage drop for long wire runs — even if the wire can handle the current, the voltage drop may be excessive.

Engineering Handbox

1. d(inches) = 0.005 × 92^((36-12)/39) = 0.0808 in 2. d(mm) = 0.127 × 92^0.615 = 2.053 mm 3. Area = π/4 × 2.053² = 3.31 mm² 4. Ampacity (NEC): 20A in 60°C insulation

VerificationAWG 12: 2.05mm diameter, 3.31mm² area. Standard for US 20-amp household circuits.

Knowledge Base

AWG番号が大きいほど太い?

いいえ、逆です。AWG 10(2.59mm)はAWG 24(0.51mm)よりはるかに太い。

AWG→mmの計算式は?

d(mm) = 0.127 × 92^((36-AWG)/39)。3 AWGステップで断面積が約2倍。

15Aに必要なAWGは?

AWG 14が最低基準(米国NEC)。20A:AWG 12。30A:AWG 10。長距離ではサイズアップ。

メートル法の対応は?

AWG 10≈6mm²、12≈4mm²、14≈2.5mm²、18≈1.0mm²。IEC規格(mm²)が北米以外の世界標準。

単線とより線の違いは?

同じAWG = 同じ断面積 = 同じ抵抗 = 同じ許容電流。より線は柔軟、単線は形状保持に優れる。